Fire­fighting Equipment

Feuer-NP3000-2.jpg
Technology and AccessoriesDIN EN 1028DIN EN 1028 classifies firefighting centrifugal pumps with priming system.

Guarantee points


DIN EN 1028 defines 3 guarantee points, that the pump has to reach:
  • Nominal performance at nominal pressure and a geodetical suction lift of 3 m at a determined nominal speed
  • 50 % of the nominal performance at nominal pressure and a geodetical suction lift of 7.5 m
  • 50 % of the nominal performance at 1.2-fold nominal pressure and a geodetical suction lift of 3 m


Classified products

JOHSTADT firefighting centrifugal pumps classified to DIN EN 1028: